en

DOMESTIC WASTEWATER TREAT. PLANT NECOR 30 D2

0PK00532
Add to Wishlist
22.117 €
Description
Domestic wastewater treatment plant type ACO NECOR 30 D2 by means of a moving bed biofilm reactor system (MBBR), manufactured in glass-reinforced plastic (GRP), in horizontal format for installation underground. With treatment capacity for 30 users and a hydraulic demand of 4,5 m³/day, with high purification performance in compliance with RD 509/1996 and UNE-EN 12566-3. Solution consisting of 1 compact equipment with dimensions 5332mm long, 2000mm wide and 2150mm high. With inlet connection and outlet DN160 and aeration DN110 DN160. Total installed power: 960W. Weight: 825kg.
Code:0PK00532
Characteristics
Benefits
  • Compact water treatment plant.
  • Easy installation and maintenance.
  • Low power consumption.
Areas of application
  • Equipment for the treatment of sewage in small and medium-sized communities.
Decanter
  • Anaerobic degradation of the accumulated organic matter
Reactor
  • Removal of organic matter and nutrients
  • Including recirculation system by pump
  • Includes turbine type compresor for 1-3mm bubble air diffusers
Clarifier
  • Sludge recirculation by pumping.
BOD5 (mg/l) <14
  • COD (mg/l) <68
  • SS (mg/l) <15
  • Effluent qualities
Effluent qualities
  • BOD5 (%) = 95
  • COD (%) = 89
  • SS (%) = 96
  • The equipment is designed to treat waste water with the following composition: BOD5: 400ppm, COD: 600ppm, SS: 450ppm
Stages of operation:
  • The system is carried out in the following stages:
  • 1- Primary decanter: In this process, the decanting and sedimentation of a large part of the sedimentation of a large part of the suspended matter suspended matter present in the wastewater
  • 2- Biological reactor: Biological decomposition of organic matter takes place in the reactor thanks to the supply of air and the generation of aerobic microorganisms.
  • 3- Clarifier: The sludge resulting from the decomposition of the organic matter is settled inside the clarifier. The decanted sludge is recirculated back to the primary clarifier by pumping.
Technical Specifications
Dimensions 1
Model:
NECOR 30
EH:
30
Hydraulic demand (m³/day):
4,5
Weight (kg):
825
Dimensions 2
H (mm):
2150
H1 (mm):
1810
H2 (mm):
1600
TD (mm):
327
DN:
160
DN2:
50
L
(mm):
5332
A (mm):
2000

ACO. we care for water