en

GREY WATER REUSE PLANT GREM 1500 VS

0PK00306
Add to Wishlist
22.937 €
Description
Grey water treatment and reuse plant type ACO GREM 1500 VS by means of membrane technology made of glass-reinforced plastic (GRP) in vertical format for above ground installation. With a reclaimed water capacity of 1500 l/day and a maximum filtration capacity of 3000 l/day in compliance with the UNE-EN 16941-2:2021 standard and Royal Decree 1085/2024. Solution consisting of 1 equipment of dimensions 1847mm long, 2113mm wide and 1900mm high. With inlet connection DN110, outlet DN 50 and overflow DN110 and with 3 access covers to the interior of the equipment, 1 access cover of dimensions 667x495 mm made in glass-reinforced plastic (GRP) and 2 access covers of dimensions 1xØ410 1xØ313 mm made in polyethylene. Includes screen, membrane blower, chlorination system and control panel.Total installed power: 173w Peso: 533,2 kg.
Article:0PK00306
Characteristics
Benefits
  • Reduction of drinking water consumption from the building's network.
  • Sustainable solution and great economic savings.
  • Helps to conserve the environment.
  • Compact equipment: Roughing, oxidation, membrane filtration, chlorination and accumulation in a single unit.
Areas of application
  • Membrane filtration greywater treatment equipment for use in buildings:
    - Flushing of WC cisterns.
    - Sprinkler irrigation of gardens.
    - Exterior cleaning.
Filter pass-through 1mm.
  • Grinding
  • Manufactured in PVC.
Start-stop float system.
  • 0.1 micron pitch ultrafiltration membranes.
  • Total power 173W.
  • Maximum power consumption 2,9kWh/m³.
  • Membrane bioreactor
  • Biological decomposition of organic matter.
  • Air supply by compressor.
Chlorination and accumulation
  • Circular auxiliary tank for chlorination of 100L with a diameter of 580mm and a height of 600mm.
  • Buoy system for treated water
Electric panel
  • Single-phase current 230 V
Effluent qualities
  • BOD5 (mg/l)<15
  • DWO (mg/l)<50
  • SS (mg/l) <2
  • Turbidity (UNT) <1
  • Escherichia coli (CFU/100 ml) 0
  • Nematode eggs (eggs/10 l) <1
Effluent qualities
  • BOD5 (%) = 90
  • COD (%) = 83
  • SS (%) = 98
  • Turbidity (%) = 99
  • The equipment is designed to treat waste water with the following composition: BOD5: 400ppm, COD: 600ppm, SS: 450ppm
Stages of operation:
  • 1- Roughing: This consists of removing any solids that may be carried by the water, mainly hair, which could damage the membranes.
  • 2- Biological oxidation: Biological decomposition of the organic matter takes place in the biological reactor thanks to the contribution of air and the generation of aerobic microorganisms.
  • 3- Filtration: Solid-liquid separation takes place by filtration using membrane technology. By means of a suction system, a vacuum pressure is exerted on the membranes, creating an outside-inside flow so that the water penetrates through the membranes, leaving the solids and bacteria on the outer wall. The diffusers create an upward air flow that cleans the outer wall surface of the membranes and ensures aerobic conditions.
  • 4- Chlorination and accumulation: The treated water is chlorinated by dosing sodium hypochlorite allowing the sanitary properties of the effluent to be preserved ensuring water reuse and then stored in the accumulation compartment.
Technical Specifications
Esquema GREM 1000-1500 VS
Dimensions 1
Reclaimed water
(l/day):
1500
Filtration
(l/day):
3000
Weight
(Kg):
533,2
Modelo:
GREM 1500 VS
Dimensions 2
L
(mm):
1847
A
(mm):
2113
H
(mm):
1900
H1
(mm):
1550
H2
(mm):
125
DN
(mm):
110
DN2
(mm):
50

ACO. we care for water